IEC Power transformers – Part 4: Guide to the lightning impulse and switching impulse testing – Power transformers and reactors. Edition Guide to the lightning impulse and switching impulse testing –. Power transformers and reactors. Reference number. IEC (E). INTERNATIONAL. Buy IEC Ed. Power transformers Part 4: Guide to the lightning impulse and switching impulse testing – Power transformers and reactors from SAI.

Author: Arashikree Faerr
Country: Guatemala
Language: English (Spanish)
Genre: Travel
Published (Last): 25 April 2017
Pages: 190
PDF File Size: 12.71 Mb
ePub File Size: 16.19 Mb
ISBN: 483-7-40833-136-1
Downloads: 82302
Price: Free* [*Free Regsitration Required]
Uploader: Nagar

Documents Flashcards Grammar checker. Guide to the lightning impulse and switching impulse testing — Power transformers and reactors This English-language version is derived from the original bilingual publication by leaving out all French-language pages.

Missing page numbers correspond to the Frenchlanguage pages. Reference number IEC Consolidated editions The IEC is now publishing consolidated versions of its publications. For example, edition numbers 1.

Information relating to this publication, including its validity, is available in the IEC Catalogue of publications see below in addition to new editions, amendments and corrigenda. Information on the subjects under consideration and work in progress undertaken by the technical committee which 6007-4 prepared this publication, as well as the list of publications issued, is also available from the following: On-line information is also available on recently issued publications, withdrawn and replaced publications, as iex as corrigenda.

Please contact the Customer Service Centre see below for further information. The object of the IEC is to promote international co-operation on all questions 06076-4 standardization in the electrical and electronic fields.

Their preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with may participate in this preparatory work.

International, governmental and non-governmental organizations liaising with the IEC also participate in this preparation. The IEC collaborates closely with the International Organization for Standardization ISO in accordance with conditions determined by agreement between the two organizations.

Any divergence between the IEC Standard and the corresponding national or regional standard shall be clearly indicated in the latter. The IEC shall not be held responsible for identifying any or all such patent rights.

This International Standard cancels and replaces IEC published in and constitutes a technical revision of that document. The text of this standard is based on the following documents: Annexes A and B are for information only. Temperature rise Part 3: Insulation levels, dielectric tests and external clearances in air Part 4: Guide to lightning impulse and switching impulse testing — Power transformers and reactors Part 5: Ability to withstand short-circuit Part 8: Application guide Part Determination of sound levels The committee has decided that the contents of this publication will remain unchanged until Guide to the lightning impulse and switching impulse testing — Power transformers and reactors 1 Scope This part of IEC gives guidance and explanatory comments on the existing procedures for lightning and switching impulse testing of power transformers to supplement the requirements of IEC It is also generally applicable to the testing of reactors see IECmodifications to power transformer procedures being indicated where required.

IEC | IEC Webstore

Information is given on waveshapes, test circuits including test connections, earthing practices, failure detection methods, test procedures, measuring techniques and interpretation of results.

For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document including any amendments applies. IECHigh-voltage test techniques — Part 1: Insulation levels, dielectric tests and external clearances in air IEC60076- IECInstruments and software used for measurement in high-voltage impulse tests — Part 1: Requirements for instruments IECDigital recorders for measurements in high-voltage impulse tests — Part 2: The practice of 600766-4 impulse generation with discharge of a separate capacitor into an intermediate or low-voltage winding is also applicable.

However, the method which employs an additional inductance in series with the capacitor to provide slightly damped oscillations transferred into the highvoltage winding is not applicable. Alternative means of switching impulse generation or simulation such as d. Different considerations in the choice of test circuits terminal connections for lightning and ie impulse tests apply for transformers and reactors.

On transformers, all terminals and windings can be lightning impulse tested to specific and independent levels. In switching impulse testing, however, because of the magnetically transferred voltage, a specified test level may only be obtained 660076-4 one winding see IEC Whilst, on reactors, lightning impulse testing is similar to that on transformers, i.

  ENUMITEM LATEX PDF

Hence, in this standard, lightning impulse testing is covered by a common text for both transformers and reactors whilst switching impulse testing is dealt with separately for the two types of equipment. This basic arrangement is shown in figure 1. The effective L thowever, may be influenced by the terminal treatment. It varies between the leakage inductance L s for short-circuited terminals and L o for open-circuited terminals.

More details in this respect are given in 7. 6007-64 front time T 1 is determined mainly by combination of the effective surge capacitance of the test object, including C Land the generator internal and external series resistances. The time to half-value T 2 is, for lightning impulses, primarily determined by the generator capacitance, the inductance of the test object and the generator discharge resistance or any other parallel resistance.

However, there are cases, for example, windings of extremely low inductance, where the series resistance will have a significant effect also on the wavetail. For switching impulses, other parameters apply; these are dealt with in clause 8. The test equipment used in lightning and switching impulse applications is basically the same. Differences are in details only, such as values of resistors and capacitors and the terminal connections of the test object.

To meet the different requirements of the waveshape for lightning and switching impulses, due consideration has to be given to the selection of the impulse generator parameters, such as capacitance and series and discharge parallel resistances. While the output voltage of the impulse generator is determined by the test levels of the windings with respect to their highest 60067-4 for equipment U m for the test object, the required energy storage capability is essentially dependent on the inherent impedances of the test object.

A brief explanation of the principles of waveshape control is given in annex A. The arrangement of the test plant, test object and the interconnecting cables, earthing strips, and other equipment is limited by the space in the test room and, particularly, the proximity effect of any structures.

During impulse testing, zero potential cannot be assumed throughout the earthing systems due to the high values and rates of change of impulse currents and voltages and the finite impedances involved.

Online Collections

Therefore, the selection of a proper reference earth is uec. It is good practice to firmly connect this current return path to the general earth system of the test room, preferably close to the test object. This point of connection should be used as reference earth and to attain good earthing of the test object it should be connected to the reference earth by one or several conductors of low impedance see IEC The voltage measuring circuit, which is a separate loop ief the test object carrying only the iev current and not any major portion of the impulse current flowing through the windings under test, should also be effectively connected to the same reference earth.

In switching impulse testing, since the rates of change of the impulse voltages and currents are much reduced compared with those in a lightning impulse test and no chopping circuit 600076-4 involved, the problems of potential gradients around the test circuit and with respect to the reference earth are less critical.

Nevertheless, it is suggested that, as a precaution, the same earthing practices should be followed as used irc lightning impulse testing. Before a test, an overall check of the test circuit and the measuring system may be performed 600766-4 a voltage lower 600766-4 the reduced voltage level. In this check, voltage may be determined by means of a sphere gap or by comparative measurement with another approved device.

When using a sphere gap, it should be recognized that this is only a check and does not replace the periodically 6007-64 calibration of the approved measuring system. After any check has been made, it is essential that neither the measuring nor the test circuit is altered except for the removal of any devices for checking. Information on types of voltage dividers, their applications, accuracy, calibration and checking is given in IEC The surge capacitance of the transformer under test being constant, the series resistance may have to be reduced in an attempt to obtain the correct front time T 1 or rate of rise, but the reduction should not be to the extent that oscillations on the crest of the voltage wave become excessive.

  IBN E INSHA URDU KI AAKHRI KITAB PDF

In such an event, a compromise between the extent of allowable oscillations and the obtainable front time is necessary.

Search results for “”

The value of the test voltage is determined according to the principles of IEC The inductance of such windings may be so low that the resulting waveshape is oscillatory. This problem may be solved to some extent by the use of large capacitance within the generator, by parallel stage operation, by adjustment of the series resistor or by specific test connections of the terminals idc windings not under test or, in addition, of the non-tested terminals of windings under test.

Impedance earthing, rather than direct earthing, of the non-tested winding terminals results in a significant increase in the effective inductance. For directly earthed terminals, only the leakage inductance determined by the short-circuit impedance is involved. For impedance earthed terminals, ie main inductance becomes predominant. This can make the effective inductance to times greater than with direct earthing. With this limitation, guidance for selecting impulse generator capacitance and adjusting waveshapes is given in annex A.

Hence, it is not possible to state a time to chopping which is the most onerous either in general or for any particular transformer or reactor. Oscillograms or digital recordings of chopped waves, however, are 60076-4 comparable for almost identical times to chopping. This, in fact, represents a guideline for the arrangement of the ie circuit and may entail the introduction of additional impedance Z c in this circuit to meet the limit see figure 1. On multiple layer windings, the layer impedance may damp the 600076-4 normally to the extent that it does not oscillate around zero see figure B.

The recommendation in IEC to use a triggered-type chopping gap is made because of its advantage in obtaining consistency of the time to chopping, thereby facilitating the comparison of oscillographic or digital recordings not only 600076-4 but also after chopping.

600076-4 latter part will only be comparable for reasonably identical times to chopping. Normally the non-tested terminals of the phase winding under test are earthed and the 6076-4 phase windings are shorted and earthed.

However, in order to improve the wavetail T 2resistance earthing of the non-tested windings may be advantageous see clause 5 and 7. In addition to the methods of waveshape adjustment in 7. When non-linear elements or surge diverters — built into the transformer or 60706-4 — are installed for the limitation of transferred overvoltage transients, the impulse test procedure should be discussed in advance for each particular case.

Refer also to IEC Different transients can be recorded and used separately or in combination, as shown in figure 2.

These are listed a to e below.

It is essential, in acceptance testing, to record at least one of these transients in addition to the applied test voltage: The sum of items ac and d or of items bc 6076-4 dis sometimes referred to as line current. When testing reactors, both of the shunt and series types, items c and e are inapplicable; item d may be applied but only as an additional means of transient recording since it is likely to be less sensitive than when used in transformer testing.

The preferred method of test is that of direct application although in special cases where the intermediate or low-voltage winding cannot, in service, be subjected to lightning overvoltages from the system connected to it, the “transferred surge” method may alternatively be employed.

The eic test of the low-voltage winding is then carried out simultaneously with the test of the associated high-voltage winding. In these conditions, the waveform of the transferred voltage does not conform with that specified in IEC It is more important to try to obtain the required voltage level by means of termination resistors of sufficiently high value. However, this may not always be possible even with the highest values of resistors.

In this test, high inter-phase voltages may occur on delta-connected windings and the danger of overstressing inter-phase insulation, internal or external, may limit the voltage that can be applied to the low-voltage winding.